For wind you need to consult an appropriate design guide such as ASCE 7-05.
Wind loading on a structure is a VERY complicated subject.
Currently there are two approaches.
A) A desktop or analytic approach of estimating wind loads using design codes such as ASCE7-05.
B) Hiring a wind expert to construct a physical model and and calculate wind pressures measured directly from a wind tunnel test.
A) will allow you to derive a site specific wind design pressure based on the height of the building, surface roughness, site location etc. Typically you then multiply this pressure by an appropriate co-efficent in the code for a given building shape.
The other atypical method it to use numerical approaches such as CFD. This approach is not yet accepted due to nuances such as of surface roughness.
Building deflection is again subjective. Doing a modal analysis and getting an idea of the frequency is better. You can increase the frequency by playing about with the building stiffness.
You need to modify the stiffness of the building to get the deflection down. i.e. play about with geometry, add extra members with stiffness, reduce weight, use material with higher elastic modulus etc
If you are getting a 7m deflection for a 400m building then I can right away that is way too soft. That is equivalent to 400m/7m or H/57. You want to be at least H/500 to H/1000 so aim for 80 to 40 mm.
Your wind load seems reasonable at 87 psf for that height of building